Free Tool
Duct Static Pressure Calculator
Work out the pressure loss of industrial or commercial ductwork (straight-duct friction, fittings, filters and other components, corrected for air temperature and altitude), and from it the static pressure a fan must overcome. Airflow rate plus that pressure (SP) is the duty point you take into selecting a fan.
Built for process exhaust, machinery and equipment ducting, and factory and warehouse ventilation, as well as commercial ventilation and air handling unit retrofits. It is not a residential HVAC duct design tool, and it does not cover dust or material conveying.
What the Calculator Adds Up
The calculator adds up the pressure losses the air encounters along the longest or most restrictive path of the ventilation system, so the duct layout matters as much as the duct sizes. It assumes air is drawn from, and discharged to, spaces at the same pressure, usually the atmosphere. If the equipment you draw from or the space you discharge into is held at a different pressure, enter the difference (outlet space minus inlet space) as a fixed pressure difference. It is added as entered, without the safety margin.
The losses fall into four groups:
| Part | Where the loss comes from | How the calculator handles it |
|---|---|---|
| Straight duct friction | Wall shear (viscous friction) along the duct; depends on air velocity, duct cross-section dimensions, length and wall roughness, including seams and joints | Darcy–Weisbach equation with a friction factor from the Colebrook equation, for each section |
| Fittings | Turbulence in every bend, elbow, transition, tee, damper, screen and entry | Loss coefficient × velocity pressure, fitting by fitting |
| Components | Filters, coils, louvers, silencers, fire dampers, grilles, make-up air openings | Pressure drop from the component datasheet; filters can be sized at their final (loaded) pressure drop |
| Exit loss | The velocity pressure of air leaving the duct, which is lost once it discharges into the room or outside | Counted once, as the exit fitting of the last section (coefficient 1.0 for an abrupt discharge); not added again on top of the fittings |
In the worked example below, straight duct is only about 13% of the calculated pressure loss, and the loaded filter and the outlet fittings make up most of the rest. In long runs with few fittings, the balance shifts toward friction.
At the same velocity, a mitered elbow produces about eight times the pressure loss of a smooth-radius one. If you want the background on what static pressure is and how it is measured, see fan static pressure explained.
Published loss coefficients show how wide the range is:
| Fitting | Loss coefficient C |
|---|---|
| 90° smooth round elbow, r/D = 1.5 | 0.15 |
| 90° mitered round elbow, no vanes | 1.2 |
| Opposed-blade damper, fully open | 0.52 |
| Insect screen, 70% free area | 0.58 |
| Abrupt discharge to atmosphere | 1.0 |
Source: ASHRAE, Principles of HVAC, 9th ed., online supplement "Fitting Loss Coefficients" (values after Idelchik 1986, Locklin 1950 and Brown & Fellows 1957).
How Duct Pressure Drop Is Calculated
Every section of the duct is calculated separately, then the losses are added. All calculation is done in SI units; imperial inputs are converted first.
1. Air density. The calculator works in volumetric airflow (air volume per hour or per minute), so it needs the density of the air being moved. Atmospheric pressure at the site altitude h (in metres) comes from the standard atmosphere, then density from the ideal gas law:
p = 101,325 × (1 − 2.25577 × 10⁻⁵ × h)^5.25588
ρ = p ÷ (287.05 × T), with T in kelvinAt 20 °C and sea level this gives 1.204 kg/m³.
2. Velocity and velocity pressure. For each section, V = Q ÷ A and velocity pressure Pv = ½ρV². Rectangular ducts use the hydraulic diameter Dh = 2WH ÷ (W + H).
3. Friction factor. The Reynolds number Re = V·Dh ÷ ν decides the flow regime. At normal design velocities duct flow is turbulent, and the friction factor f comes from the Colebrook equation, solved by iteration:
1/√f = −2 log₁₀( (ε/Dh) ÷ 3.7 + 2.51 ÷ (Re √f) )
where ε is the absolute roughness of the duct wall, for example about 0.09 mm, a published average for galvanized steel round duct with longitudinal seams and joints every 1.2 m (4 ft). Below Re 2,300 (in ventilation ducts this takes very low velocities, for example near the bottom of the system curve), the laminar value f = 64/Re is used; results between Re 2,300 and 4,000 are flagged as transitional.
4. Straight duct loss. ΔPf = f × (L ÷ Dh) × Pv
5. Fitting losses. ΔPk = C × Pv, where Pv is taken at the reference section defined by the coefficient's source table. For transitions that is the upstream section. For the two tee types in the calculator, a converging round tee and a diverging 90° tee, it is the combined-flow section, with separate coefficients for the main and branch paths. Some coefficients also depend on Reynolds number, which the calculator applies automatically.
6. Components. By default, a datasheet pressure drop is taken as rated at standard air (1.2 kg/m³) and scaled to the actual air density. This is a simplifying assumption. Where the manufacturer gives the pressure drop at your actual airflow and air conditions, enter that value and switch the density correction off for that component.
7. Total. System pressure = (duct losses + component losses) × (1 + safety margin) + any fixed pressure difference. Results are shown in pascals and in inches of water column (in. wg). By default the path runs between two spaces at the same pressure and includes the exit loss, so this total is the fan total pressure the system needs. A fixed pressure difference between the inlet and outlet spaces, if you enter one, is part of that balance, and the total is still the fan total pressure. If you enter the fan outlet size, the calculator also gives the required fan static pressure, using the definition in AMCA 210: fan total pressure minus the velocity pressure at the fan outlet.
8. System curve. The whole calculation is repeated from zero to 1.5 times the design airflow to draw the system curve, rather than assuming pressure rises exactly with the square of flow. Components follow a flow exponent of 2 unless you set another; a fixed pressure difference stays the same at every flow. The curve is drawn in system (fan total) pressure. If you enter the fan outlet size, it is also given as required fan static pressure, with the outlet velocity pressure subtracted at each flow, for comparison with static-pressure fan curves.
Checks behind the numbers: the friction factor matches three Moody chart reference points within 1% and the explicit Haaland formula within 2%, and the worked example below was reproduced by a separately written implementation. Loss coefficients are entered from the source tables and interpolated linearly between table values. Inputs beyond a table's range, including the Reynolds-number corrections, use the nearest table value and are flagged in the results; combinations the tables give no data for are refused.
Worked Example: Equipment Exhaust Duct
An exhaust fan draws air out of a piece of process equipment through a panel filter and discharges it outside through the roof.
| Input | Value |
|---|---|
| Design airflow | 2,400 m³/h (1,413 CFM) |
| Air | 25 °C, sea level → ρ = 1.184 kg/m³ |
| Section 1 | Round 355 mm, 6 m, galvanized steel; flush entry from the equipment plenum, one 90° elbow (r/D 1.5), reducer to 315 mm (30° included angle) |
| Section 2 | Round 315 mm, 12 m, galvanized steel; two 90° elbows (r/D 1.5), round butterfly damper fully open, insect screen (70% free area), stackhead at the roof |
| Filter | ISO ePM10 panel filter, 50 Pa clean; sized at the recommended final pressure drop that filter datasheets give for ePM classes under EN 13053: the lower of 50 + 100 Pa and 3 × 50 Pa = 150 Pa |
| Safety margin | 10% |
| Fan outlet | 315 mm round |
| Result | Value |
|---|---|
| Duct losses (both sections) | 146.4 Pa |
| Filter at final pressure drop (density-corrected) | 148.0 Pa |
| System pressure before margin | 294.4 Pa |
| System pressure with 10% margin | 323.8 Pa (1.30 in. wg) |
| Velocity pressure at the 315 mm fan outlet | 43.3 Pa |
| Required fan static pressure | 280.5 Pa (1.13 in. wg) at 2,400 m³/h |
| Step | Section 1 (355 mm) | Section 2 (315 mm) |
|---|---|---|
| Air velocity | 6.7 m/s | 8.6 m/s |
| Velocity pressure | 26.9 Pa | 43.3 Pa |
| Friction factor | 0.0180 | 0.0179 |
| Friction loss per metre | 1.37 Pa/m | 2.47 Pa/m |
| Straight duct loss | 8.2 Pa | 29.6 Pa |
| Fitting coefficients | entry 0.50 + elbow 0.15 + reducer 0.05 = 0.70 | elbows 0.30 + damper 0.19 + screen 0.58 + stackhead 1.00 = 2.07 |
| Fitting loss | 18.9 Pa | 89.7 Pa |
The loaded filter accounts for about half of the calculated pressure loss at design airflow (148 of 294 Pa). Had the fan been sized for the clean filter, the requirement would have come out at 215 Pa instead of 324 Pa, leaving the fan undersized by about 108 Pa once the filter loads.
The outlet end comes next. Stackhead and insect screen together add about 68 Pa, while all 18 m of straight duct come to less than 38 Pa.
Repeating the full calculation at other airflows gives the system curve: about 82 Pa at half the design airflow and about 465 Pa at 120% of it, with the filter following the square of airflow (the default exponent) and the friction factor recalculated at each flow.
From Duty Point to Fan
Static or total pressure
Check which pressure the fan curve shows before you compare. Many performance curves plot static pressure against airflow; compare those with the required fan static pressure, not with the system total. The two differ by the velocity pressure at the fan outlet, 43 Pa in the example. Reading a static-pressure curve against the system total mixes two pressure definitions: it overstates the static pressure needed and can lead to an oversized fan.
Where the fan will run
At a given speed, a fan runs where its curve crosses the system curve, so read both with the same pressure definition and the same air density: a fan total-pressure curve against the system curve, or a static-pressure curve against the fan-static version of the system curve, shown when you enter the fan outlet size. If the curve at that speed passes above the duty point, the fan delivers more air than planned unless it is slowed down or throttled; if it passes below, the airflow falls short. For a given airflow and pressure, a fan running near its best-efficiency region draws less power. Noise depends on more than efficiency, so check the sound data separately. How to read a fan curve walks through finding that intersection.
Below the results, the calculator runs this check against the full-speed fan static pressure curves of our EC centrifugal fans and lists up to three preliminary matches: the models with the least excess airflow at full speed, compared conservatively with the system total pressure. Select one to see its estimated operating point on your system curve. Treat it as a first match: the curve supplied with a quotation is the one that counts, and an engineer still checks sound data and site conditions.
As filters load, system resistance rises and a fixed-speed fan slides back along its curve to a lower airflow, which is why the calculator sizes filters at their final pressure drop by default. An EC fan fitted with constant-airflow control can speed up to hold the airflow as the filter loads, within the limits of its maximum speed and available pressure; see static pressure vs airflow fans and how to control an EC fan. For speed changes in general, the fan laws calculator scales a fan's airflow, pressure and power with speed; the new operating point is still where the scaled curve meets the system curve.
Hot air and high sites lower air density. Duct losses in pascals fall with density, and so does the pressure a fan produces at a given speed. Catalogue curves are published at a stated reference density, such as the AMCA standard air density of 1.2 kg/m³. Check the density stated on the curve, enter it if it is different, and compare the curve with the requirement the calculator converts to that density.
Backward-curved centrifugal fans are a common option for ducted systems with filters and several fittings, while axial fans suit lower-resistance applications that move air in large volumes. The right fan type and fan size are settled by the duty point and the curves, not by the kind of system alone.
Add this duty point to my inquiry
Prefer to check models yourself? Try the EC centrifugal fan selector.

EC Centrifugal Fans
Speed-controllable backward-curved fans for filtered and ducted systems

DC Centrifugal Fans
Backward-curved fans for equipment running on DC power

AC Centrifugal Fans
Fixed-speed backward-curved fans for mains-powered ventilation

EC Axial Fans
High airflow for low-resistance runs, condensers and coolers
Send Your Duty Point to an Engineer
Send the airflow and pressure from the calculator, plus the voltage, available space and control signal (0–10 V, PWM or Modbus) if you know them. You get a fan recommendation checked against the performance curve, with a reply within 1 business day.

Duct Static Pressure FAQ
How do you calculate duct static pressure?
To calculate static pressure for a duct system, add the pressure losses along the most restrictive path: straight-duct friction from the Darcy–Weisbach equation, each fitting as its loss coefficient times the velocity pressure, plus the datasheet pressure drop of filters, coils and other components. The calculator does this section by section and corrects for air density. To verify the result on an existing system, compare it with a field measurement taken at suitable measuring planes and corrected for velocity pressure; two static pressure readings either side of the fan are not, on their own, the fan pressure.
Should I compare the result with the fan's static pressure or total pressure curve?
Check which one the curve shows. Many catalogue curves are static pressure; compare those with the required fan static pressure: the system total minus the velocity pressure at the fan outlet. Enter the fan outlet size to get that figure. If a specification gives a "total static pressure", check which losses it includes before comparing it with either figure.
How much pressure does an elbow add?
An elbow adds its loss coefficient times the velocity pressure. A smooth round elbow with a centreline radius of 1.5 times the diameter has a coefficient of about 0.15; a sharp mitered elbow without turning vanes is about 1.2. At 8 m/s in standard air (1.2 kg/m³), velocity pressure is roughly 38 Pa, so that is about 6 Pa against 46 Pa per elbow.
Should I size the fan for clean or dirty filters?
Size it for the loaded filter, or the airflow will drop as the filter fills. For ISO ePM1, ePM2.5 and ePM10 filters, manufacturers' datasheets citing EN 13053 (the European standard for air handling units) give the recommended final pressure drop as the lower of the initial value plus 100 Pa and three times the initial value. For ISO Coarse filters, at least one manufacturer gives the lower of initial plus 50 Pa and three times initial; check your filter's datasheet. The calculator applies the rule for the class you choose, unless you enter the manufacturer's final pressure drop or switch it off. For industrial filters outside that scope, use the manufacturer's figure.
How do temperature and altitude affect duct pressure drop?
Lower air density means lower pressure losses for the same volumetric airflow, but the fan also produces proportionally less pressure. Convert the requirement to the reference density of the catalogue curve (for example 1.2 kg/m³, AMCA standard air) before comparing; the calculator shows that converted value.
How much safety margin should I add?
The default is 10%, a general allowance for uncertainty in fitting coefficients and component data at the preliminary selection stage. It is not a leakage correction. Where leakage is significant it changes the airflow in each section, so add it to the section airflows instead. A loaded filter is an operating condition, not a margin; do not add a second margin on top of it, and avoid stacking margins at every step.
Can I use this calculator for dust collection or material conveying?
No. Conveying systems are designed around a minimum transport velocity and the extra pressure needed to carry the material, which this calculator does not model.
References & Limitations
References
- ASHRAE. Principles of Heating, Ventilating, and Air Conditioning, 9th ed., online supplement "Fitting Loss Coefficients" (2021).
- Idelchik, I.E., et al. Handbook of Hydraulic Resistance, 2nd ed. Hemisphere, 1986.
- ASHRAE. ASHRAE Handbook—Fundamentals, 2021, Chapter 21 (duct design).
- Colebrook, C.F. "Turbulent flow in pipes, with particular reference to the transition region between the smooth and rough pipe laws." Journal of the Institution of Civil Engineers, 1939.
- EN 13053:2019, Ventilation for buildings — Air handling units — Rating and performance for units, components and sections (recommended final filter pressure drop by ISO 16890 class, as applied in filter manufacturers' datasheets).
- ANSI/AMCA 210-16 (ASHRAE 51-16), Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating (standard air; fan total, velocity and static pressure definitions).
Limitations
- This is a pressure loss calculator for preliminary fan selection, not a full duct design. It assumes steady, fully developed flow in each section. For project design, use a full fitting database such as the ASHRAE Duct Fitting Database.
- The inlet and outlet of the path are assumed to be at the same pressure, normally atmospheric. Any other pressure difference has to be entered as a fixed pressure difference, which does not change with airflow or air density.
- Fitting coefficients come from published data, and sources do not always agree. Close-coupled fittings can interact (published studies mainly cover pairs of elbows), so their combined loss can differ from the sum of the individual values.
- Duct leakage, fan inlet and outlet system effects, and temperature change along the duct are not included.
- Component pressure drops come from the datasheet values you enter, density-corrected from standard air unless you switch that off. On the system curve, components follow a flow exponent of 2 by default; filter pressure drop can rise less steeply than that, and the exponent depends on the filter, so it can be changed per component.
- Transitions between round and rectangular duct, and rectangular converging tees, use the nearest round or rectangular table and are marked as approximate.
- The fan check covers only our EC centrifugal fans at full speed, using catalogue curves spot-checked against the published charts. The curves were measured at room temperature and 65% relative humidity; the reference air density was not specified, so 1.2 kg/m³ is assumed for this preliminary comparison. The outlet area of each model is not included, so the static-pressure curves are compared with the system total pressure, which is conservative. Fans that would run below a quarter of their maximum airflow are not listed. Other fan types, and fans in parallel or series, are not covered.
- Not for dust collection or pneumatic conveying.
Disclosure: This calculator is built and maintained by Proventofan, an industrial fan manufacturer. The duty point calculation does not depend on any product data; only the fan check below the results uses our own fan curves.
Disclaimer: Results are estimates for preliminary selection. Confirm the duty point against the fan's performance curve and site conditions before ordering; our engineers can check it for you.
Cite this tool: <a href="https://www.proventofan.com/tools/duct-static-pressure-calculator/">Duct Static Pressure Calculator</a> by Proventofan