Duct Velocity Calculator: FPM to CFM and CFM to FPM

This duct air velocity calculator converts velocity to airflow, or airflow to velocity, for round and rectangular ducts. You can also size a duct for a target velocity, or turn pitot tube velocity pressure readings into velocity (and, from an equal-area traverse, an average velocity). Results are shown in both imperial (fpm, CFM) and metric (m/s, m³/h, L/s) units.

Built for industrial and commercial ventilation: checking what a fan is really moving through a duct, or choosing a duct size before you work out the pressure the fan has to overcome. The relationship is simple: CFM = FPM × duct area in square feet.

Airflow is calculated from the inside cross-sectional area and the average velocity (actual airflow, not corrected to standard conditions). Pitot conversion assumes standard air: V (fpm) = 4005 × √VP (in. wg); no density correction is applied. Results are rounded to 4 significant figures.

02 / Units

FPM, CFM and Duct Area

FPM (feet per minute, also written ft/min or LFM, linear feet per minute) is a velocity: how fast the air moves. CFM (cubic feet per minute) is an airflow, or volume flow rate: how much air passes in a minute. The duct's cross-sectional area links the two. Multiply velocity by area and you get airflow; divide airflow by area and you get the average velocity.

The metric equivalents are m/s for velocity and m³/h or L/s for airflow. 1 m/s is 196.9 fpm, 1,000 fpm is 5.08 m/s, and 1 CFM is 1.699 m³/h or 0.4719 L/s. If you only need to convert airflow units, our m³/h to CFM calculator does that directly.

To work out how much airflow a space or process needs in the first place, see our guide to fan CFM calculation.

Two details change the answer more than people expect:

  • Use the inside dimensions. Area comes from the inside diameter, or the inside width and height. Internal insulation or a liner makes the free area smaller than the outside size suggests.
  • The airflow is at the conditions in the duct. CFM calculated from an actual average velocity and the area is actual airflow at the air's temperature and pressure, not standard CFM (SCFM). This calculator does not convert between the two. When the velocity comes from pitot readings, it is calculated for standard air (see below).
03 / Quick Tables

Duct CFM Quick Tables

Airflow at common duct sizes and velocities, calculated with the same formulas and rounding as the calculator. The answer to "how many CFM will a 12 × 12 duct carry" depends on the velocity: 1,000 CFM at 1,000 fpm, 2,000 CFM at 2,000 fpm. These tables are geometry only; they are not recommended sizes.

Round ducts, airflow in CFM
Inside diameter (in)500 fpm1,000 fpm1,500 fpm2,000 fpm
698.17196.3294.5392.7
8174.5349.1523.6698.1
10272.7545.4818.11,091
12392.7785.41,1781,571
14534.51,0691,6042,138
16698.11,3962,0942,793
18883.61,7672,6513,534
201,0912,1823,2724,363
241,5713,1424,7126,283
Rectangular ducts, airflow in CFM
Inside size (in)500 fpm1,000 fpm1,500 fpm2,000 fpm
8 × 6166.7333.3500666.7
12 × 8333.3666.71,0001,333
12 × 125001,0001,5002,000
16 × 12666.71,3332,0002,667
24 × 121,0002,0003,0004,000
24 × 181,5003,0004,5006,000
Round ducts, metric, airflow in m³/h
Inside diameter (mm)2.5 m/s5 m/s7.5 m/s10 m/s
10070.69141.4212.1282.7
150159318.1477.1636.2
200282.7565.5848.21,131
250441.8883.61,3251,767
315701.41,4032,1042,806
4001,1312,2623,3934,524
5001,7673,5345,3017,069
04 / How to Calculate

How to Calculate Duct Velocity and CFM

From velocity to airflow: CFM = FPM × A, where A is the inside cross-sectional area in square feet. For a round duct, A = π × D² ÷ 4; for a rectangular duct, A = width × height. Work in feet, or divide an area in square inches by 144.

From airflow to velocity: FPM = CFM ÷ A.

To size a duct: A = CFM ÷ target FPM. For a round duct, D = √(4A ÷ π); for a rectangular duct, divide the area by the side you already know.

In metric units, m³/h = m/s × m² × 3600, and L/s = m/s × m² × 1000.

Example 1: airflow in a 12 in round duct at 1,000 fpm. A = π × (1 ft)² ÷ 4 = 0.7854 ft². CFM = 1,000 × 0.7854 = 785.4 CFM (1,334 m³/h). A metric example with its own numbers: a 300 mm duct (slightly smaller than 12 in, which is 304.8 mm) at 5 m/s has an area of 0.07069 m² and carries 0.3534 m³/s, which is 1,272 m³/h.

Example 2: a duct for 2,000 CFM at 1,500 fpm. A = 2,000 ÷ 1,500 = 1.333 ft². For a round duct, D = √(4A ÷ π) = 1.303 ft, or 15.64 in (397.1 mm). For a rectangular duct 24 in wide (2 ft), the height is 1.333 ÷ 2 = 0.6667 ft, or 8 in, an aspect ratio of 3 : 1.

The calculated diameter may not match an available duct size. At 2,000 CFM, a 16 in round duct gives about 1,432 fpm and a 14 in duct about 1,871 fpm. Check the velocity of the size you actually select with the Airflow → Velocity tab. The calculation is geometry only: it does not include pressure loss, leakage or fittings.

05 / Pitot Readings

From Pitot Tube Readings to Velocity

A pitot tube measures total pressure and static pressure; the difference is the velocity pressure (VP). For standard air, velocity in fpm is:

V = 4005 × √VP, with VP in inches of water gauge (in. wg).

In metric units the same relationship is V (m/s) = 1.289 × √VP (Pa). Example: a reading of 0.75 in. wg gives 4005 × √0.75 = 3,468 fpm. In an 18 in round duct (1.767 ft²) that is 6,129 CFM.

What "standard air" means. OSHA defines standard air as dry air at 68 °F (20 °C) and 29.92 in. Hg, with a density of 0.075 lb/ft³. The form V = 4005 √VP for standard air is used in common references, such as the AIHA calculator and Kele's application notes. You will also see slightly different constants: calculated from the density, 1.2041 kg/m³ gives about 4,004, 0.075 lb/ft³ gives about 4,009, and 1.2 kg/m³ gives about 4,011. Dwyer, for example, uses 4004.4 based on 70 °F and 29.92 in. Hg. 4005 itself is a rounded constant: it corresponds to about 1.204 kg/m³, slightly above OSHA's rounded 0.075 lb/ft³. All of these are within 0.15% of 4005. Hot air, high altitude or a gas other than air needs a density correction; this calculator does not apply one.

Averaging traverse readings. Velocity varies across a duct, so one reading is one point, not the average. For a traverse, take readings at equal-area points and convert each reading to velocity before you average. Averaging the pressures before taking the square root overestimates the average velocity when the readings differ. As a numerical illustration, readings of 0.04 and 1.0 in. wg correspond to 801 and 4,005 fpm, an average of 2,403 fpm. Averaging the readings first (0.52 in. wg) and then taking the square root gives 2,888 fpm, 20.19% too high. Two readings illustrate the calculation; they are not a complete field traverse. EPA's stack-gas velocity method (Method 2) averages the square roots of the readings, not the readings themselves. The calculator follows this method for multiple readings: enter one reading per line, or separate readings with semicolons. Commas are read as thousands separators, not as separators between readings.

Round duct: 2 passes at 90°, 6 points eachPass 1Pass 2Equal-area ringsRound duct2 passes at 90°, 6 points eachRectangular duct: 12 equal areas, 1 point at each centerRectangular duct12 equal areas, 1 point at each center
Example traverse layouts. Round duct: two passes at 90°, six points on each, at the positions EPA Method 1 (Table 1-2) gives for six points on a diameter; the dashed circles mark rings of equal area. Rectangular duct: the section is split into equal rectangles with one point at the center of each (EPA Method 1). How many points you need depends on where you measure. Convert each reading to velocity, then average the velocities.

Low readings. OSHA cautions that manometers are rarely usable below about 0.05 in. wg velocity pressure (12.45 Pa). By the formula above, 0.05 in. wg is about 895.5 fpm. The calculator shows a caution when a nonzero reading is below 0.05 in. wg (zero readings are handled separately). Check the resolution and accuracy of your instrument before relying on low readings.

Where to measure, how many points to take and how to read a pitot tube are covered in the measurement section of our fan static pressure guide. To convert a reading between Pa and inches of water, use our Pa to inches of water converter.

06 / Velocity and the Fan

What Duct Velocity Means for the Fan

At a fixed airflow, a smaller duct cross-section means a higher air velocity. That changes what the fan has to do:

  • Losses and noise. In otherwise comparable ductwork, higher velocity generally increases friction and fitting losses and can increase airflow-generated noise. The fan must deliver the required airflow against the system's resistance at its operating point.
  • Velocity pressure rises with the square of velocity. At 1,000 fpm its standard-air equivalent is 0.06234 in. wg (15.53 Pa); at 2,000 fpm, 0.2494 in. wg (62.12 Pa); at 4,000 fpm, 0.9975 in. wg (248.5 Pa). Doubling the velocity makes it four times larger. These values are velocity pressure, not the total system pressure loss.
  • Dust-carrying ducts need enough conveying velocity. If the velocity is too low for the material being carried, particles may settle and build up inside the duct.

There is no single duct velocity suitable for every application. In occupied buildings, airflow noise is often an important design constraint; in dust-collection systems, the velocity must also be high enough to limit settling. For industrial exhaust, OSHA's ventilation chapter describes ducts as running at roughly 2,000–6,000 fpm (about 10.16–30.48 m/s). Donaldson gives examples such as about 4,500 fpm for lead dust and 2,000–2,500 fpm for weld fume. These are descriptions and examples, not design limits for your system.

Once you have a duct size and velocity, the next number you need is the pressure the fan must overcome. Our duct static pressure calculator works out duct, fitting and filter losses from the same airflow. Then compare that pressure with the curves of our axial fans or centrifugal fans, reading the airflow at your pressure on the curve rather than the datasheet's maximum figures.

07 / Inquiry

Have a Duct and Airflow to Match?

Send us your airflow, duct size and, if you know it, the system static pressure. "Request a fan quote with these numbers" above adds the calculator result to the form; check it and add anything else before you send. We reply within 1 business day.

Proventofan fan performance test bench measuring airflow and static pressure for custom OEM fans
08 / FAQ

Frequently Asked Questions

How do you convert FPM to CFM?

Multiply the velocity in fpm by the duct's inside cross-sectional area in square feet: CFM = FPM × ft². A 12 in round duct has an area of 0.7854 ft², so at 1,000 fpm it carries 785.4 CFM.

How do I calculate FPM from CFM?

Divide the airflow by the area: FPM = CFM ÷ ft². 2,000 CFM through a 24 × 12 in duct (2 ft²) is 1,000 fpm.

How many CFM will a 12 × 12 duct carry?

It depends on the velocity. A 12 × 12 in duct has 1 ft² of inside area, so it carries 500 CFM at 500 fpm, 1,000 CFM at 1,000 fpm and 2,000 CFM at 2,000 fpm. The velocity you can accept depends on noise, pressure loss and, for dusty air, the speed needed to keep material moving.

How do I size a duct from CFM and velocity?

Divide the airflow by the target velocity to get the area, then find the diameter: D = √(4A ÷ π); for a rectangular duct, divide the area by the side you already know. For 2,000 CFM at 1,500 fpm, the area is 1.333 ft² and the diameter 15.64 in. Choose an available size, then check its velocity.

How do I convert velocity pressure to FPM?

For standard air, V = 4005 × √VP, with VP in in. wg. 0.75 in. wg gives 3,468 fpm. Multiply by the duct's inside area in ft² for CFM: in an 18 in round duct (1.767 ft²) that is 6,129 CFM. For several traverse readings, convert each one to velocity and then average the velocities.

Why do some calculators use 4004 or 4009 instead of 4005?

The constant depends on the air density taken as standard. Calculated from the density, 1.2041 kg/m³ gives about 4,004 and 0.075 lb/ft³ about 4,009. All are within 0.15% of 4005, the value used in common references such as the AIHA calculator.

Is the result actual CFM or standard CFM (SCFM)?

Actual volumetric airflow, not SCFM. When you enter the actual average velocity, multiplying it by the inside duct area gives the airflow at duct conditions. When the velocity comes from pitot readings, the calculator assumes standard air density, so results may differ under nonstandard conditions. It does not convert to SCFM.

What duct velocity should I use for industrial ventilation?

There is no single velocity for every industrial duct. The choice depends on pressure loss, noise, duct layout and whether particles must be carried without settling. OSHA describes industrial exhaust ducts as running at roughly 2,000–6,000 fpm, but that is a description, not a design recommendation. Choose a target velocity for your application, calculate the duct area from it, and check the pressure loss before you fix the duct size.

09 / Sources

References & Limitations

References

  1. Occupational Safety and Health Administration. OSHA Technical Manual, Section III, Chapter 3: Ventilation Investigation (standard air; pitot tube and traverse measurements; manometer limits at low velocity pressure; industrial duct velocities). https://www.osha.gov/otm/section-3-health-hazards/chapter-3
  2. U.S. Environmental Protection Agency. Method 2: Determination of Stack Gas Velocity and Volumetric Flow Rate (Type S Pitot Tube), 40 CFR Part 60, Appendix A, Section 12.6 (average velocity from the square roots of the velocity heads). https://www.epa.gov/sites/production/files/2017-08/documents/method_2.pdf
  3. National Institute of Standards and Technology. NIST Special Publication 811: Guide for the Use of the International System of Units (SI), Appendix B (foot, inch, foot per minute, cubic foot per minute, inch of water, conventional). https://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9
  4. AIHA. Duct Velocity and VP (IH calculator). https://www.aiha.org/ih-calculator-app/calcs/duct-velocity-and-vp.html
  5. Kele. Application Tips: Determining Air Flow in Cubic Ft./ Min (pitot velocity pressure to velocity; duct area). https://www.kele.com/content/blog/application-tips-determining-air-flow-in-cubic-ft-min
  6. Dwyer Omega. Velocity Measurement and Environmental Effects. https://www.dwyeromega.com/en-us/resources/calculating-velocity-measurement
  7. Donaldson. Understanding Conveying Velocities to Save Money in Dust Collection. https://www.donaldson.com/en/resources/technical-articles/understanding-conveying-velocities-to-save-money-dust-collection/
  8. U.S. Environmental Protection Agency. Method 1: Sample and Velocity Traverses for Stationary Sources, 40 CFR Part 60, Appendix A-1 (Table 1-2, traverse point locations in circular ducts; equal-area points in rectangular ducts). https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-60/appendix-Appendix%20A-1%20to%20Part%2060

Limitations

  • Velocity pressure is converted for standard air (V = 4005 × √VP). There is no density correction for temperature, altitude or other gases.
  • Airflow is actual airflow at duct conditions, not standard CFM.
  • Airflow is calculated from the velocity you supply and the duct's inside area. A single pitot reading is the velocity at one point and does not establish the cross-sectional average; several readings from a suitable equal-area traverse can be used to estimate it. The calculator does not check measurement locations or traverse quality.
  • Velocity pressure readings should come from a standard or calibrated pitot tube (total minus static pressure). Probes that need their own coefficient are not covered.
  • Duct sizes are geometry only: no pressure loss, leakage or fittings, and not a recommended size. A larger duct lowers velocity, which may not suit dust-carrying ducts.
  • Areas use the inside dimensions you enter.
  • The calculator does not say whether a velocity is too high or too low for your application.

Disclosure: Built and maintained by Proventofan. The calculator uses published formulas and conversion factors only and does not draw on our product data.

Disclaimer: For engineering estimates. Check critical values against measurements, drawings and the fan's own performance data.