Fan Power Calculator: Fan BHP, Shaft Power and Motor Input Power

This fan power calculator works out the shaft power a fan needs, its brake horsepower (BHP), from airflow, fan pressure and fan efficiency. Add the drive and motor to estimate the electrical input power, or enter a measured power to back-calculate efficiency. Shaft power is shown in kW and hp and electrical input power in kW, with the working shown.

Built for industrial and commercial fans: checking how much power a duty point needs, comparing a belt-driven fan with a direct-drive one, or reading an EC fan's input power against a shaft-power figure. The core relationship is shaft power = airflow × fan pressure ÷ fan efficiency, with pressure and efficiency on the same basis.

Use the same basis for pressure and efficiency: total with total, static with static.

The fan's pressure rise at the same operating airflow, not a single duct static-pressure reading or the fan's maximum catalog pressure.

At your operating point on the fan curve, not the peak, and on the same pressure basis.

Incompressible formula (no compressibility coefficient) and no air-density correction. Enter the fan pressure at actual conditions. Displayed digits keep the arithmetic consistent; they are not a measurement accuracy.

Review the prefilled details before submitting your inquiry.

02 / Power Terms

Air Power, Shaft Power (BHP) and Input Power

Four power figures sit between the wall socket and the air, and calculators often blur them:

  • Air power (air horsepower) is the fan's output to the air, calculated as airflow × fan pressure on the total or the static pressure basis. It does not include the losses inside the fan. This calculator uses the incompressible form and does not apply the compressibility correction used in fan testing (see Limitations).
  • Shaft power, or brake horsepower (BHP), is the mechanical power the fan needs at its shaft; when people say fan horsepower, this is usually what they mean. It equals air power divided by the fan efficiency on the same basis, so it is higher than air power whenever the efficiency is below 100%.
  • Required motor shaft output adds the drive. A belt loses some power between motor and fan; a direct-drive fan loses none.
  • Electrical input power adds the motor, or the motor and its controller if the efficiency you enter includes the controller's losses. A power meter reading is comparable only if it is taken at the boundary your efficiency covers (the motor terminals, or upstream of the controller if you included its losses) and at the same operating point.
Electrical inputMotor(and controller)η motor(and controller, if included)Driveη drive(1 for direct drive)Fan shaftη fan(same pressure basis)AirElectrical input powerMotor shaft outputShaft power (BHP)Air powerElectrical inputMotor(and controller)η motor(and controller,if included)Driveη drive(1 for direct drive)Fan shaftη fan(same pressure basis)AirElectrical input powerMotor shaft outputShaft power (BHP)Air power
Power flows from the electrical supply through the motor and any drive to the fan shaft and into the air. Each efficiency is the share of power passed across that stage; a direct drive has no drive loss. Fan efficiency must be on the same basis as the pressure: total with total, static with static.

Power is quoted in kilowatts or horsepower. One horsepower (550 ft·lbf/s) is 745.7 W, so 1 kW is 1.341 hp. Fan pressure is the pressure rise the fan produces between its inlet and outlet, as total pressure or as static pressure. Our article on fan static pressure explains the difference between static, velocity and total pressure.

03 / How to Calculate

How to Calculate Fan Power

The fan power calculation needs three numbers from the same operating point: airflow, fan pressure and fan efficiency.

Fan power equation (SI): P = Q × p ÷ η, with the airflow rate Q in m³/s, p in Pa and P in W. η is the fan efficiency as a decimal (0.82, not 82), on the same basis as p: total efficiency with total pressure, static efficiency with static pressure.

Shaft power (US units): BHP = CFM × p (in. wg) ÷ (6,343 × η). The constant converts CFM × inches of water into horsepower; it is about 6,343.31 when worked out from the definitions of the horsepower, the cubic foot per minute and the inch of water, and AMCA's training material on fan power uses the same 6343.

Electrical input: input power = shaft power ÷ (drive efficiency × motor efficiency). Drive efficiency is 1 for a direct drive; for a V-belt it depends on the power transmitted (see Belt losses below).

Use the efficiency at your operating point, read from the fan curve, not the fan's peak efficiency. Our guide on how to read a fan curve shows where to find the operating point, the efficiency and the BHP line.

Example 1: shaft power at a published duty point. A worked example in an AMCA article on fan efficiency grades selects fans for 10,000 cfm at 3 in. wg total pressure; one of them, a 30 in. single-inlet fan, has a total efficiency of 82%. Air power = 10,000 × 3 ÷ 6,343.31 ≈ 4.729 hp. Shaft power ≈ 4.729 ÷ 0.82 ≈ 5.768 hp, or 4.301 kW. In SI: 4.719 m³/s (16,990 m³/h) × 747.3 Pa ≈ 3,527 W, and 3,527 W ÷ 0.82 ≈ 4,301 W. The calculator keeps full precision internally (the constant is about 6,343.31) and rounds each displayed result separately, so redoing the arithmetic from the printed figures can differ in the last digit. The article lists 5.73 bhp for that fan; our figure is about 0.7% higher. The article rounds both the bhp and the efficiency, so the small difference fits their reported precision.

Example 2: adding a V-belt and the motor. At 4.301 kW of shaft power, the V-belt equation in ANSI/AMCA 207-17, evaluated at that fan shaft power, gives a drive efficiency of 94.46%, so the motor has to deliver 4.553 kW (6.106 hp) at its shaft. With a motor efficiency of 90%, the electrical input is 4.301 ÷ (0.9446 × 0.9) = 5.059 kW. The same fan on a direct drive with the same motor efficiency would draw 4.779 kW. The overall wire-to-air efficiency of the belt-driven set is 69.71%.

Example 3: efficiency from a measured shaft power. If the fan curve gives 5.73 hp at 10,000 CFM and 3 in. wg total pressure, the fan total efficiency is 4.729 ÷ 5.73 ≈ 82.54%.

04 / Static or Total?

Static or Total? Match Pressure and Efficiency

A fan at a given operating point has one shaft power. You can reach it two ways, and both give the same answer:

  • total pressure with total efficiency, or
  • static pressure with static efficiency.

ANSI/AMCA 210 defines fan static pressure as fan total pressure minus the fan's velocity pressure, and fan static efficiency as fan total efficiency multiplied by the ratio of fan static pressure to fan total pressure. So the static figures are both smaller by the same ratio, and the shaft power comes out the same.

Mixing them does not. Take the same 30 in. fan: its 76% static efficiency and 82% total efficiency imply a fan static pressure of about 3 × 76 ÷ 82 = 2.78 in. wg. Static pressure with static efficiency gives 5.768 hp, as before. Static pressure with the total efficiency gives 5.346 hp, 7.3% low. Total pressure with the static efficiency gives 6.223 hp, 7.9% high. Many online fan power calculators ask for static pressure; check which efficiency goes with it before you divide.

The pressure must also be the fan's own pressure rise at the airflow you are using, not a single static-pressure reading somewhere in the duct and not the fan's maximum catalog pressure. To work out the static pressure a duct system needs, use our duct static pressure calculator.

05 / Why Results Differ

Why Fan Power Calculators Disagree

Four things explain most of the differences you will see between calculators and catalogs.

The constant: 6,343 or 6,356. This calculator uses 6,343, which follows from the conventional inch of water (249.089 Pa, the value ANSI/AMCA 210 uses for fan testing) and matches AMCA's training material. Some published formulas use 6,356 instead. At the same airflow, pressure and efficiency, 6,356 gives a result about 0.20% lower: 5.756 hp instead of 5.768 hp in Example 1. That is small next to the other uncertainties in a preliminary power estimate, but use one constant consistently when you compare published ratings or check against a specified limit. Our Pa to inches of water converter explains the conventional inch of water.

Peak versus operating-point efficiency. A fan reaches its peak efficiency at one point on its curve. Entering the peak value for a duty point elsewhere on the curve understates the power. In the AMCA article's example, eight fan sizes could all deliver 10,000 cfm at 3 in. wg; their peak total efficiencies were 78–83%, but their total efficiencies at that duty point ranged from 40% to 83%.

Rounding. Catalog bhp and efficiency figures are rounded, so recalculating one from the other rarely matches to the last digit, as in Example 1.

Belt losses. Some calculators add a fixed 3–5% for a belt drive. The V-belt model in ANSI/AMCA 207-17 makes the loss depend on the power transmitted, and it is larger on small drives:

V-belt drive loss, calculated from the ANSI/AMCA 207-17 V-belt equation
Fan shaft powerV-belt efficiencyLoss
0.5 kW (0.6705 hp)89.27%10.7%
1 kW (1.341 hp)91.45%8.5%
2 kW (2.682 hp)93.17%6.8%
5 kW (6.705 hp)94.65%5.4%
10 kW (13.41 hp)95.27%4.7%
37 kW (49.62 hp)95.79%4.2%

The model assumes a properly tensioned belt. The U.S. Department of Energy notes that V-belt efficiency can drop by as much as 5% over time if the belt slips because it is not retensioned, and that notched belts are about 2% more efficient than standard V-belts. Our comparison of direct drive and belt drive fans covers the drive choice in more detail.

06 / Motor and Meter

From Shaft Power to the Motor and the Meter

Drive. A direct-drive fan, with the impeller on the motor shaft or rigidly coupled to it, has no drive loss. A flexible coupling is taken as 98% efficient in ANSI/AMCA 207-17, and a synchronous (toothed) belt as 94–98% depending on the power. For V-belts, see the table above. These are the transmission models from ANSI/AMCA 207-17; the standard's full fan-system calculation covers regulated polyphase induction motors only, so this page does not present its results as calculations under that standard.

Motor efficiency and the input boundary. Use the motor's efficiency at the load it will actually run at. If the fan runs on a variable frequency drive or another motor controller and you want the power drawn upstream of it, enter a combined motor-and-controller efficiency; with the motor efficiency alone, the result is the power at the motor terminals.

EC fans. EC fan catalogs, including ours, often list electrical input power for the whole unit, motor and electronics included. Compare that figure with this calculator's electrical input power, not with a shaft power or BHP figure, and only when both refer to the same operating point. If you know the overall (wire-to-air) efficiency at that point, you can enter it directly. Do not combine a catalog's maximum airflow, maximum pressure and maximum input power as if they were measured at one operating point. Fan efficiency index (FEI) ratings are also based on wire-to-air power; see our guide to fan efficiency and FEI.

Choosing a motor size. This calculator does not pick a motor rating, but a few principles from fan makers and the U.S. Department of Energy apply:

  • The motor has to meet or exceed the fan's BHP at the operating point, plus the belt loss on a belt-driven fan. A direct-driven fan can be sized to match or exceed the fan BHP.
  • Check every operating point the fan may see, not only the design point. The DOE's fan sourcebook notes that forward-curved fans have a power curve that rises steadily with airflow toward free delivery, so the motor must be chosen carefully to avoid overloading; backward-inclined fans have a power curve that peaks and then drops off at high airflow (a "non-overloading" characteristic), which is why they are often chosen when system behavior at high airflow is uncertain.
  • On a variable frequency drive, the horsepower a motor can deliver depends on speed: AAON notes that an inverter-duty motor running below its rated speed provides proportionally less horsepower. Check the motor and drive ratings against the BHP at the operating speed rather than assuming the nameplate horsepower is available at every speed.

Before the final choice, also check starting torque and current, the supply voltage, the speed range, ambient temperature, motor cooling and overload capability: running BHP alone does not show that a motor suits the application.

Read the power line on the fan curve across the whole range you expect; our guide on how to read a fan curve shows how. For the cost of running a fan once you know its power, see how many kW an axial fan uses, and for the effect of a speed change, the fan laws calculator. When you have a duty point, our axial fans and centrifugal fans list EC and AC options; compare their curves at your airflow and pressure rather than their maximum figures.

07 / Inquiry

Have a Duty Point to Match?

Send us your airflow, fan pressure and the power or efficiency you are working with. "Request a fan quote with these numbers" above adds the calculator result to the form; check it and add anything else before you send. We reply within 1 business day.

Proventofan fan performance test bench measuring airflow and static pressure for custom OEM fans
08 / FAQ

Frequently Asked Questions

How do you calculate fan brake horsepower (BHP)?

Divide the air power by the fan efficiency. In US units, BHP = CFM × fan pressure (in. wg) ÷ (6,343 × efficiency). Use static pressure with static efficiency, or total pressure with total efficiency. At 10,000 CFM, 3 in. wg total pressure and 82% total efficiency, BHP ≈ 5.768 hp (4.301 kW).

Should I use static or total pressure in the fan power formula?

Either, as long as the efficiency is on the same basis: static pressure with static efficiency, total pressure with total efficiency. Both give the same shaft power. Mixing them gives the wrong answer; for the fan above, static pressure with the total efficiency understates the power by 7.3%.

Why do some formulas use 6356 instead of 6343?

This calculator uses 6,343, which follows from the conventional inch of water (249.089 Pa, as in ANSI/AMCA 210); some formulas use 6,356. For the same airflow, pressure and efficiency, 6,356 gives a BHP about 0.20% lower.

How do I convert fan BHP to kW or to motor input power?

Multiply hp by 0.7457 for kW: 5.768 hp is 4.301 kW. For electrical input, divide the shaft power by the drive efficiency and the motor efficiency: with a V-belt (94.46%) and a 90% motor, 4.301 kW becomes 5.059 kW.

How much power does a belt drive lose?

It depends on the power transmitted. The ANSI/AMCA 207-17 V-belt model gives about 8.5% at 1 kW of fan shaft power and about 4.2% at 37 kW, for a properly tensioned belt. A slipping belt loses more; a direct drive loses none.

How do I calculate fan efficiency from measured power?

Divide the air power by the measured shaft power: 4.729 hp ÷ 5.73 hp ≈ 82.54%. If you measured electrical input power instead, the result is the overall efficiency of fan, drive and motor together, not the fan's own efficiency, and the airflow, pressure and power must all be at the same operating point.

Is fan BHP the same as motor horsepower?

No. BHP is what the fan needs at its shaft at one operating point. The motor's rated horsepower is what it can deliver. The motor has to cover the BHP plus any belt loss across the operating range; a motor rated close to the BHP at one point may be overloaded at another.

Is there a direct CFM to horsepower conversion?

No. Shaft power depends on airflow, fan pressure and fan efficiency at the same operating point. At 10,000 CFM and 82% total efficiency, it is 1.923 hp at 1 in. wg total pressure and 11.54 hp at 6 in. wg; at 3 in. wg total pressure and 60% total efficiency it is 7.882 hp.

09 / Sources

References & Limitations

References

  1. Air Movement and Control Association International. ANSI/AMCA Standard 210-16, Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating, Sections 3.1.16 (inch of water, 249.089 Pa), 3.1.26–3.1.28 (fan total, velocity and static pressure), 3.1.30–3.1.34 (compressibility coefficient, fan output power, fan total and static efficiency).
  2. Air Movement and Control Association International. ANSI/AMCA Standard 207-17, Fan System Efficiency and Fan System Input Power Calculation, Section 2 (scope) and Section 4.1.2 (V-belt, synchronous belt, flexible coupling and direct-drive transmission efficiency).
  3. AMCA International and Twin City Fan & Blower. Fundamentals of Airflow (training presentation, 2020), Section 3: Power and Efficiency (air horsepower, brake horsepower, static and total efficiency). https://www.amca.org/assets/resources/public/assets/uploads/FINAL-_Fundamentals_of_Airflow-_TCF-_AMCA__5.6.20.pdf
  4. Tim Mathson and Michael Ivanovich. AMCA's Fan Efficiency Grades: Answers to Frequently Asked Questions (AMCA International), Table 2: fan selection example for 10,000 cfm at 3 in. Pt. https://staging.amca.org/assets/resources/public/userfiles/file/Nospreads_FanEfficGrades.pdf
  5. U.S. Department of Energy. Improving Fan System Performance: A Sourcebook for Industry (forward-curved and backward-inclined power curves; motor overloading). https://docs.nlr.gov/docs/fy03osti/29166.pdf
  6. U.S. Department of Energy. Replace V-Belts with Notched or Synchronous Belt Drives, Energy Tips: Motor Systems. https://www.energy.gov/sites/prod/files/2014/04/f15/replace_vbelts_motor_systemts5.pdf
  7. National Institute of Standards and Technology. NIST Special Publication 811, Appendix B (horsepower, cubic foot per minute, inch of water). https://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9
  8. AirPro Fan & Blower Company. Fan Brake Horsepower: Size Matters When Selecting Fan Motors (2019). https://blog.airprofan.com/brake-horsepower-selecting-fan-motors/
  9. AAON. How do you choose a motor that meets your required fan brake horsepower (BHP)? https://www.aaon.com/resources/how-do-you-choose-a-motor-that-meets-your-required-fan-break-horsepower-bhp
  10. John Bade and Armin Hauer. Fan-System Comparisons Made Reliable With AMCA 207, HPAC Engineering, March 2019 (belt-drive assumptions of ANSI/AMCA 207). https://www.hpac.com/association-solutions/article/20929792/fan-system-comparisons-made-reliable-with-amca-207

Limitations

  • Incompressible formula: ANSI/AMCA 210 multiplies fan output power by a compressibility coefficient; this calculator does not. The difference grows with pressure, so for high-pressure blowers use the manufacturer's rated power.
  • No air-density correction. Enter the fan pressure for the actual operating conditions; if the performance data are rated for standard air (1.2 kg/m³), account for the actual air density before using them.
  • Efficiency must be the fan's efficiency at your operating point, on the same pressure basis as the pressure you enter.
  • Belt and coupling efficiencies use the ANSI/AMCA 207-17 transmission models, not measurements. Motor efficiency is the value you enter; it is not adjusted for load.
  • The results do not represent calculations under ANSI/AMCA 207-17, which covers regulated polyphase induction motors only.
  • System effects and poor inlet or outlet conditions change the operating point itself; they are not part of the power formula.
  • Electrical input power is an estimate of power at one operating point, not energy use over time.
  • The required motor shaft output is shown without a sizing margin, and the calculator does not recommend a motor rating.
  • Displayed digits keep the arithmetic consistent; they are not a measurement accuracy.

Disclosure: Built and maintained by Proventofan. The calculator uses published formulas, conversion factors and drive-efficiency models only and does not draw on our product data.

Disclaimer: For engineering estimates. Check critical values against the fan's and motor's own performance data.