Skip to the converter

Free Tool

Pa to Inches of Water Converter

Convert a pressure between pascals (Pa) and inches of water column (in. wc, also written in. wg or inH₂O), with millimeters of water (mm H₂O), kilopascals (kPa) and millibars (mbar) alongside and a psi readout. Type in any field and the others update as you type.

Built for fan, duct and air handling pressures: a fan datasheet in Pa against a specification in in. wg, or a manometer reading in one unit against a drawing in another. 1 in. wc ≈ 249.09 Pa, and 1 Pa ≈ 0.0040146 in. wc.

psi (result only)

This converter uses conventional water-column units, not values for a particular water temperature: 1 mm H₂O = 9.80665 Pa and 1 in. wc = 25.4 mm H₂O = 249.08891 Pa. NIST SP 811 lists 249.0889 Pa per conventional inch of water; AMCA 210 uses 249.089 Pa per inch for fan testing. Converted values are rounded to five significant figures, except values of 100,000 or more, which are rounded to the nearest whole number.

02 / Unit Names

in. wc, in. wg and inH₂O: One Unit, Several Names

The labels in. wc (inches of water column), in. wg (inches of water gauge), inH₂O and "inches of water" all refer to the same unit: the pressure at the bottom of a column of water one inch high. The abbreviation WC means "water column" but does not, by itself, say whether inches or millimeters are meant. The metric unit is mm H₂O (also run together as mmH₂O), also written mmWC or mmAq: the pressure of a column one millimeter high. Both are defined with the same water density (1,000 kg/m³) and standard gravity, so 1 in. wc is exactly 25.4 mm H₂O, the same ratio as an inch to a millimeter.

Which unit you meet depends mostly on where the document comes from. US specifications and many US sources use inches of water. Datasheets in SI units give Pa or kPa, and some still give mm H₂O. Our own tables are split the same way: most of our product lines list static pressure in Pa, while our DC brushless fan tables use mm-H₂O.

Gauge pressure is measured relative to local atmospheric pressure, while a differential pressure is measured between two points. Fan and duct readings can use either reference. This converter changes the units only: it does not determine the pressure type or convert between gauge and absolute pressure.

03 / Conversion Tables

Pa to Inches of Water Conversion Tables

A quick conversion chart for common values from 10 to 5,000 Pa and from 0.05 to 10 in. wc. Converted values use the same rounding rules as the converter.

Pa to in. wc and mm H₂O
Pain. wcmm H₂O
100.0401461.0197
250.100372.5493
500.200735.0986
750.30117.6479
1000.4014610.197
1250.5018312.746
1500.6021915.296
2000.8029320.394
2501.003725.493
3001.204430.591
4001.605940.789
5002.007350.986
7503.01176.479
1,0004.0146101.97
1,5006.0219152.96
2,0008.0293203.94
2,50010.037254.93
5,00020.073509.86
In. wc to Pa and mm H₂O
in. wcPamm H₂O
0.0512.4541.27
0.124.9092.54
0.249.8185.08
0.2562.2726.35
0.374.7277.62
0.499.63610.16
0.5124.5412.7
0.75186.8219.05
1249.0925.4
1.5373.6338.1
2498.1850.8
2.5622.7263.5
3747.2776.2
4996.36101.6
51,245.4127
61,494.5152.4
81,992.7203.2
102,490.9254
04 / How to Convert

How to Convert Pa to Inches of Water

The pascal to inches of water formula uses a single factor. To convert pascals (Pa) to inches of water column (in. wc), divide by 249.08891. To convert inches of water to Pa, multiply by 249.08891:

  • in. wc = Pa ÷ 249.08891
  • Pa = in. wc × 249.08891
  • mm H₂O = Pa ÷ 9.80665, and Pa = mm H₂O × 9.80665
  • in. wc = mm H₂O ÷ 25.4
  • kPa = Pa ÷ 1,000, and mbar = Pa ÷ 100

Example 1. A US specification asks for 0.9 in. wg. 0.9 × 249.08891 = 224.18 Pa, or 22.86 mm H₂O. If a fan curve is plotted in Pa, compare 224.18 Pa with the same pressure type on the curve, at the required airflow. The conversion alone does not show whether a fan meets the duty point.

Example 2. A datasheet gives 35 mm H₂O. 35 × 9.80665 = 343.23 Pa, and 35 ÷ 25.4 = 1.378 in. wc.

Negative readings convert the same way, and the converter keeps the minus sign. It does not determine the measurement reference or the pressure type.

For a quick check in your head, 1 in. wc is about 250 Pa and 1 mm H₂O is about 10 Pa. The first is 0.4% high and the second about 2% high: fine for catching a misplaced decimal point, but use the exact factors when you compare figures.

Fan pressures look tiny in psi: 1 in. wc is only 0.036127 psi.

05 / Why Results Differ

Why Converters Give Slightly Different Answers

Look up this conversion in a few places and you will find several factors: 249.08891, 249.082, 248.84, 249, or 0.004 the other way round. Some of the differences come from the reference conditions used to define an inch of water. Others come from rounding the factor. Rounded factors are useful for quick estimates, but they do not give identical results.

The conventional inch of water assumes water at exactly 1,000 kg/m³ under standard gravity. NIST SP 811 lists it as 249.0889 Pa, and AMCA 210, the laboratory test standard for fan performance, uses the same conventional conversion, rounded to 249.089 Pa per inch of water. This converter uses 249.08891 Pa per conventional inch of water, calculated from 25.4 × 9.80665 Pa per millimeter of water.

NIST also lists an inch of water at 39.2 °F (4 °C), 249.082 Pa, and at 60 °F, 248.84 Pa. The first is 0.003% below the conventional value and the second 0.1% below. Rounded factors move further: 249 is 0.04% low, and multiplying by 0.004 instead of dividing by 249.08891 gives a result 0.36% low.

250 Pa in inches of water with each factor
FactorBasis250 Pa =
249.08891 Pa per in.Conventional; 25.4 × 9.80665 (NIST SP 811 and AMCA 210 publish it rounded)1.0037 in. wc
249.082 Pa per in.Water at 39.2 °F (4 °C)1.0037 in. wc
248.84 Pa per in.Water at 60 °F1.0047 in. wc
249 Pa per in.Rounded1.004 in. wc
× 0.004Rounded reciprocal1 in. wc

Relative to the conventional conversion used here, each of these differs by less than 0.4%. Differences in reference conditions, conversion factors or rounding rules can change the last displayed digit, so a difference between converters does not, by itself, mean that a datasheet is wrong.

06 / Fan Pressures

Reading Fan Pressures in Pa and Inches of Water

A converted number only helps if both numbers mean the same thing. Check three things before you compare a requirement with a fan:

  1. The same kind of pressure. Static pressure, total pressure and velocity pressure all convert the same way, but they are not interchangeable. Our guide to fan static pressure explains the difference and how to read it on a datasheet.
  2. A point on the curve, not the two maximums. The maximum static pressure and maximum airflow on a datasheet are the two extremes of the fan's curve, not one operating point. Convert your required pressure, then read the airflow at that pressure on the curve.
  3. The pressure your system actually needs. If you need an estimate of duct system losses, our duct static pressure calculator calculates them from the duct, fitting and filter data you enter and shows the result in Pa and in. wg. For the airflow side of the duty point, use our m³/h to CFM calculator.

For a sense of scale, Aerovent's fan engineering notes give these typical static pressure ranges. They are one manufacturer's figures, not design limits, and other sources draw the lines differently.

Typical static pressure by fan type (Aerovent)
Fan typein. wgPa (converted)
Lightweight commercial panel and ring fans (wide, single-thickness blades)Generally below ½Below about 125
Tubeaxial fansUp to 4Up to about 1,000
Vaneaxial fans, single stage2 to 10About 500 to 2,500
Forward-curved centrifugal fansUp to 6; most applications 3 or lessUp to about 1,500; most about 750 or less
Backward-inclined centrifugal fansUp to 20; up to 40 with special constructionUp to about 5,000; about 10,000 with special construction

Our axial fans and centrifugal fans list static pressure in Pa, and our DC brushless fans in mm-H₂O. If your specification is in in. wg, convert it here before you compare it with those tables.

07 / Inquiry

Have a Duty Point to Check?

Send us your airflow and pressure values in the units you have. If known, include whether the pressure is static or total and where it was measured. "Add this pressure to my inquiry" above copies the converted value into the form. We reply within 1 business day.

Proventofan fan performance test bench measuring airflow and static pressure for custom OEM fans
08 / FAQ

Frequently Asked Questions

Is inH₂O the same as in. wc or in. wg?

Yes. InH₂O, in. wc (inches of water column), in. wg (inches of water gauge) and "inches of water" are the same unit. 1 in. wc = 25.4 mm H₂O ≈ 249.09 Pa.

How many pascals are in 1 mm of water?

1 mm H₂O (also written mmWC or mmAq) is 9.80665 Pa, often rounded to 9.81 Pa. The other way, 1 Pa is 0.10197 mm H₂O.

What is 1 pascal in inches of water?

1 Pa = 0.0040146 in. wc, so 250 Pa is just over 1 in. wc (1.0037 in. wc).

How do I convert in. wg per 100 ft to Pa/m?

Multiply by 8.1722. 100 ft is 30.48 m, so 1 in. wg per 100 ft = 249.08891 Pa ÷ 30.48 m = 8.1722 Pa/m. The other way, 1 Pa/m = 0.12237 in. wg per 100 ft. To work out the friction loss of a duct itself, use our duct static pressure calculator.

How many inches of water are in 1 psi?

1 psi = 27.68 in. wc, and 1 in. wc = 0.036127 psi. The converter shows psi as a read-only result, because a fan pressure of a few inches of water is only about a tenth of a psi.

Does it matter whether the reading is static, total or velocity pressure?

Not for the conversion: a pascal is a pascal, so 250 Pa of static pressure and 250 Pa of total pressure both convert to 1.0037 in. wc. It matters when you compare the number with a fan curve, which shows either static or total pressure. Our guide to fan static pressure explains the difference.

09 / Sources

References & Limitations

References

  1. National Institute of Standards and Technology. NIST Special Publication 811: Guide for the Use of the International System of Units (SI), Appendix B.9 (inch of water, conventional; inch of water at 39.2 °F and at 60 °F; millimeter of water, conventional; millibar; pound-force per square inch).
  2. ANSI/AMCA 210-16 / ASHRAE 51-16, Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating, Section 3.1.16 (conventional conversion of 1 in. of water to 249.089 Pa).
  3. Aerovent. Fan Engineering FE-2300: Fan Performance Characteristics of Axial Fans.
  4. Aerovent. Fan Engineering FE-2400: Fan Performance Characteristics of Centrifugal Fans.

Limitations

  • The converter uses the conventional inch and millimeter of water (water at 1,000 kg/m³, standard gravity). An inch of water at 39.2 °F or 60 °F differs by up to 0.1%.
  • It converts units only. It does not tell you whether a pressure is right for a particular fan; that depends on the operating point on the fan's curve. What kind of pressure a value is (static, total, a manometer reading) is up to you.
  • A datasheet's maximum static pressure and maximum airflow are two extremes of the curve, not one operating point.
  • Accepted values: 0, or 0.01 Pa to 1,000,000 Pa in magnitude, positive or negative.

Disclosure: Built and maintained by Proventofan. The converter uses published conversion factors only and does not draw on our product data.

Disclaimer: For engineering estimates. Check critical values against the original datasheet or specification.

Request a Quote